TITLE: |
||
|
|
|||
|
DOCUMENT ID: |
Installed
Monitoring Out-if-Service |
||
|
|
|||
If an
installed ODH monitoring devices is out-of-service perform the following measures:
Step 1:
Post
a warning at the entrance to the area.
Include appropriate:
·
“Temporary
Posting” verbiage, and
·
“Entry
Requirements.”
Step 2:
Submit
a Facilities Management
Work Request for repair of the unit.
Step 3:
Upon
completion of repair, remove the posting.
|
Area ODH Classification |
Time Limit |
Without Temporary Monitoring (Restricted Entry) |
With Temporary Monitoring (Unrestricted Entry) |
||
|
Temporary Posting |
Entry Requirements |
Temporary Posting |
Entry Requirements |
||
|
ODH 0 |
No
Limit |
Not
Required |
Not
Required |
Not
Required |
Not
Required |
|
ODH 1 |
8
days |
“KEEP
OUT – Potential ODH Area” |
ODH
Qualified Class
0, 1, 2, 3 |
“Temporary ODH
Monitoring in Place” |
Temporary
Monitoring + ODH
Qualified |
|
ODH 2/3 |
28
days |
“KEEP
OUT – Potential ODH Area” |
ODH
Qualified Class
0, 1, 2, 3 |
“Temporary ODH
Monitoring in Place” |
Temporary
Monitoring + ODH
Qualified Class
0, 1, 2, 3 |
|
ODH 4 |
Immediate
Repair |
“DANGER
- KEEP OUT Potential
ODH Area” |
ODH
Qualified Class
0, 1, 2, 3, 4 |
“DANGER
- KEEP OUT Potential ODH Area” |
No
Entry Allowed |
|
|
ISSUING
AUTHORITY |
TECHNICAL POINT-OF-CONTACT |
APPROVAL
DATE |
EXPIRATION
DATE |
REV. |
|
|
|
ESH&Q Division |
N/A |
N/A |
N/A |
|