On Apr 3, 2009, at 2:07 PM, Elton Smith wrote:
> #* Matt: Mentioned that CLEO had good success with the following
> scheme
> for cooling their drift chamber electronics: Fill space with (dry)
> N2. Use
> polyethelne tubing with cooling liquid (PF200) to cool N2. System was
> robust and inexpensive.
I looked up the numbers on this -- the total power radiated by CLEO
preamps was about 150W. This seems significantly (about 10x?) less
than the numbers I remember for the SiPMs. So, I'm not sure this type
of solution works.